LR2050
Continuous level sensor (guided wave radar)
LR0000B-ER34AKSKG/US
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — LR2050-01 — 30.11.2022 —
Application
Special feature
Gold-plated contacts
Media
Liquids; oil-based media; hydrous media
Dielectric constant of the
medium
≥ 1,8; (for media with a dielectric constant of 1.8...5
(e.g. oils), a coaxial pipe is needed for operation)
Recommended media
water; hydrous media; oils; oil-based media
Process temperature [°C]
-20...100; (see note under remarks)
Pressure rating [bar]
16
Vacuum resistance [mbar]
-1000
MAWP (for applications
according to CRN)
[bar]
16
Electrical data
Operating voltage [V]
18...30 DC
Current consumption [mA]
< 50
Protection class
III
Reverse polarity protection
yes
Power-on delay time [s]
< 3
Measuring principle
guided wave radar
Inputs / outputs
Number of inputs and outputs
Number of digital outputs: 1; Number of analogue outputs: 1
Outputs
Total number of outputs
2
Output signal
switching signal; analogue signal; IO-Link
Electrical design
PNP/NPN
Number of digital outputs
1
Output function
normally open / normally closed; (parameterisable)
Max. voltage drop switching
output DC
[V]
2.5
Permanent current rating of
switching output DC
[mA]
150; (200 (...60 °C))
Number of analogue outputs
1
Analogue current output [mA]
4...20, invertible; (scalable)
Max. load [Ω]
500
Short-circuit protection
yes
Type of short-circuit
protection
pulsed
Overload protection
yes
Measuring/setting range
Probe length L [mm]
150...2000
Active range A [mm]
L-40 (L-60); (when set to oil and oil based media)
Inactive range I1 / I2 [mm]
30 / 10 (30); (when set to oil and oil based media)
Sampling rate [Hz]
4